TFD - Fire #217 & #216 fire damaged rental units.
Address:

Entered Date:

08/12/2023

Applicant:

N/A

Description:

Completed Inspections

Case Status: Closed - Resolved
Case Number: CE-VIO0823-05079
Case Description: TFD - Fire #217 & #216 fire damaged rental units.
Total Completed Inspections - 2
End Date Description Inspector Results Comments
08/12/2023 COT - ENFC - Code Enforcement - Initial In Violation TFD- Commercial motel fire fire damaged rental units. #217 completely damaged and #216 small amount of damaged. Electrical turned off at disconnect box. Gas line tested. Pressure test passed. Gas line is not compromised. Shut down 216, 217, 218. 219 and 218 missing smoke detectors. Electrical panels upstairs and down stairs on bldg b work space area is blocked by storage. Gas water heater has storage around it as well as chemicals. Issued NOV's will fu on 8/14/23 ** Had 217, 216, 219 shut down. Requested for a Licensed Electrician to evaluate the electrical system for fire damage to electrical system.
08/16/2023 COT - ENFC - Code Enforcement - Follow Up Passed Followed up: Smoke detectors installed, batteries installed into smoke detectors, storage in disconnect and gas water heater removed and storage located outside on the east side of property removed. Fire extinguishers installed. Owner is currently working with their insurance company for repairs to the damaged rental units. Close case