Case: CE-VIO0224-00612
Case Details
Status:
Closed - Resolved
Type:
RMIN : UNIT # 220 - Electrical circuits shut off when using the heaters provided by management
Address:
Entered Date:
02/14/2024
Applicant:
N/A
Description:
Completed Inspections
Case Status: Closed - Resolved
Case Number: CE-VIO0224-00612
Case Description: RMIN : UNIT # 220 - Electrical circuits shut off when using the heaters provided by management
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2024 | COT - ENFC - Code Enforcement - Initial | In Violation | 1235 PM - Tried calling complainant on 5/2, no ans, left message. Visited site and attempted contact, no ans at the unit. -VM | |
| 01/31/2025 | COT - ENFC - Code Enforcement - Follow Up | Passed | 127 pm - Both outlets in dining room tested correctly. Kitchen outlet replaced with GFCI. Tested outlet, it is wired correctly. Tested GFCI and it functions as intended. Outlet in master bedroom cover is secure and outlet is secure in wall. Violations abated, close case. -VM |