Inspection Status: Scheduled
Inspection History: COT - ENFC - Code Enforcement - Follow Up
Case Number - CE-VIO0224-00612
Inspection Description - COT - ENFC - Code Enforcement - Follow Up
Inspection Status - Scheduled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
COT - ENFC - Code Enforcement - Follow Up | Scheduled | |||
05/13/2024 | COT - ENFC - Code Enforcement - Follow Up | In Violation | 237 pm - Contact w/ resident at unit. Concerns for floor not meeting baseboards. There are small areas where this is true, however there are not holes large enough to pose a tripping hazard. Concerns for roaches. Did find one dead roach on a dust pan in the kitchen. I checked kitchen cabinets, counters, and stove, and could not locate any other insects. Tenant did state had issues w/ electric cutting out or tripping breakers when using space heaters. Stated did have issues w/ others. Tested outlet in dining area, has an open neutral. Outlet next to fridge is not GFCI protected. Outlet in master bedroom is loose, cover is cracked. -VM |