Inspection History Details
Inspection Status: Passed
Inspection History: COT - ENFC - Code Enforcement - Follow Up
Case Number - CE-VIO0224-00612
Inspection Description - COT - ENFC - Code Enforcement - Follow Up
Inspection Status - Passed
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2025 | COT - ENFC - Code Enforcement - Follow Up | Passed | 127 pm - Both outlets in dining room tested correctly. Kitchen outlet replaced with GFCI. Tested outlet, it is wired correctly. Tested GFCI and it functions as intended. Outlet in master bedroom cover is secure and outlet is secure in wall. Violations abated, close case. -VM | |
| 05/13/2024 | COT - ENFC - Code Enforcement - Follow Up | In Violation | 237 pm - Contact w/ resident at unit. Concerns for floor not meeting baseboards. There are small areas where this is true, however there are not holes large enough to pose a tripping hazard. Concerns for roaches. Did find one dead roach on a dust pan in the kitchen. I checked kitchen cabinets, counters, and stove, and could not locate any other insects. Tenant did state had issues w/ electric cutting out or tripping breakers when using space heaters. Stated did have issues w/ others. Tested outlet in dining area, has an open neutral. Outlet next to fridge is not GFCI protected. Outlet in master bedroom is loose, cover is cracked. -VM |