Case Description: RMIN- Water Intrusion
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/06/2023 | COT - ENFC - Code Enforcement - Initial | In Violation | Mini Splits install without permits in a non-code compliance manner without proper ampacity or a labeled circuit breaker. Water heater was installed in a non-code compliance manner without permits or approvals from the city of Tucson. Rear porch has been installed without permits in a non-code compliant manner its location violates proper clearances for the energized service drop. Multiple nonmetallic sheeting conductors have been installed at the exterior of the residence without protective conduit, watertight seals, bushings, and legible ampacity label on over current protection device. Extension cord inside the kitchen energizing a stove hood system against the UL listing and the noncompliance manner. Roof eve has been covered with T1-11, the residence stucco meets the t1-11 not allowing proper roof ventilation. Inside the single family residence there is water intrusion, ceiling paint is bubbling as if moisture is penetrating from the rooftop. Kitchen ceiling also has paint blistering as if moisture is penetrating from the rooftop. | |
09/15/2023 | COT - ENFC - Code Enforcement - Follow Up | Completed |