Date - 08/17/2026 3:07 a.m.
Number Of Permits - (1)
| Permit | Status | Apply Date | Expired Date | Unit | Type | Description |
|---|---|---|---|---|---|---|
| T20CM08647 | Final | 12/10/2020 | 12/20/2021 | COMBO | Existing meter is inside building. Move service outside. Upgrade service from 3 phase 200amp to 3 phase 400amp. Install TEP CT can with meter. Set 6x6 N3R gutter next to CT can. Feed (2) 200amp fused disconnects from CT can. One disconnect is for future use, no new load planned at this time. One disconnect is to refeed panel A that is existing. Install 2" conduit from panel A disconnect to panel A with 4-3/0 THHN Cu. wires and #6 ground. No new loads added. |