Permit Number: T99CM03220
Parcel: Unknown

Address:
1575 E 36TH ST

Review Status: Completed

Review Details: REVISION

Permit Number - T99CM03220
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2001 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1. REMOVE ALL COMFORT STATION ELECTRICAL FROM THIS PLAN . THE STATE OF AZ. WILL REVIEW THE ASSOCIATED WIRING OF THE MODULAR BUILDING. UPON APPROVAL PROVIDE THE CITY OF TUCSON WITH THE STATE APPROVED STAMPED COPY OF THE PLANS.
2.PROVIDE POLE BASE DETAIL SHOWING DEPTH,WIDTH,REBAR, ANCHOR BOLTS, CONCRETE P.S.I. ,ETC..
3.PROVIDE A FAULT CURRENT ANALYSIS.
4. INSTALL GROUNDING ELECTRODE SYSTEM AT EACH RAMADA AND CONNECT TO 5KVA MINI POWER ZONE PER N.E.C.
5.SHOW ALL H.R.'S AND CIRCUITING AT FIXTURES AND RECEPTACLES
09/17/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2001 DELMA ROBEY OUT TO CUSTOMER Completed