Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T99CM01960
Parcel: 10603034A

Review Status: Stopped

Review Details: COMMERCIAL NEW

Permit Number - T99CM01960
Review Name: COMMERCIAL NEW
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Installation does not comply with Sec314.1 & 314.2UMC1994. 2. Provide GAMA date to support the vent sizing. 3. Show on the plans where the condensate line will run and size of same on the plans. 4. Show on the llaundry room plans how the installation will comply with Sec 908.2UMC1994.
01/02/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1.Provide the UP & DOWN stream M.H. Rim Elev. on the site plan. 2. Provide a water demand calculation based on Appendix A UPC1994 for each building on the plan. 3. Provide a clean out at each washing machine. 4. Venting in the isometric drawings does not comply with Sec 904.1UPC1994. 5. Fix the gas line isometric drawings, See P-3 red lines.
01/18/2001 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied 1. SEE PRIOR COMMENT #2. PROVIDE DETAILS AND FIRE TEST DATA ON DRAWINGS. 2. SEE PRIOR COMMENT #3. 3. SEE PRIOR COMMENT #4. 4. SEE PRIOR COMMENT #5. PROVIDE LETTER FOR PLAN REVIEW. 5. SEE PRIOR COMMENT #6. NEED LETTER PER ABOVE ITEM. 6. SEE PRIOR COMMENT #7. PROVIDE FIRE TEST DATA AND CONFORMING DETAILS ON DRAWINGS. 7. SEE PRIOR COMMENT #12. PROVIDE DETAILS & STRUCTURAL CALCULATIONS FOR GUARDRAILS AND HANDRAILS. 8. SEE PRIOR COMMENT #13. SPECIFY INSULATION ; MATERIAL, FLAME-SPREAD & SMOKE-DEVELOPMENT. 9. SEE PRIOR COMMENT # 14. SHOW MATERIALS, LOCATION, FASTENING OF FIRE -BLOCKING. 10. SEE PRIOR COMMENT #16. DETAILS & FIRE TEST DATA. 11. SEE PRIOR COMMENT #17. DETAILS & FIRE TEST DATA. 12. SEE PRIOR COMMENT #18. ADDRESS/ SHOW HOW DETAIL COMPLIES. 13. SEE PRIOR COMMENT #19. 14. SEE PRIOR COMMENT # 21. SHOW FINISHED GRADES, AS REQUESTED. 15. SEE PRIOR COMMENT #22. 16. SEE PRIOR COMMENT #23. PROVIDE STAIRWAY DESIGN PER UBC SEC #1006. 17. SEE PRIOR COMMENT # 24. SHOW ACCESSIBILE PATH. 18. SEE PRIOR COMMENT #25. 19. SEE PRIOR COMMENT #26. 20. SEE PRIOR COMMENT #27. DISPERSE PARKING SPACES REQ'D. 21. SEE PRIOR COMMENT #28. DRYVIT - ICBO ER # 2728 - NOT ALLOWED BY THIS REPORT IN TYPE V, R1 BLDGS. 22. SEE PRIOR COMMENT # 29. 23. SEE PRIOR COMMENT #32. PROVIDE SPECIFICATIONS ON DRAWINGS FOR INSULATION. 24. SEE PRIOR COMMENT #34. 25. SEE PRIOR COMMENT #36. PROVIDE COMPLETED " SPECIAL INSPECTION AND TESTING AGREEMENT " INCLUDING SPECIAL INSPECTOR QUALIFICATIONS PER UAC SEC #306.3. 26. SEE PRIOR COMMENT #37. PROVIDE COMPLETED CERTIFICATE. 27. SEE PRIOR COMMENT #38 . PROVIDE REVISED SOILS REPORT. 28. SEE PRIOR COMMENT #40. PROVIDE REQUESTED DESIGN ANALYSIS. WHERE ARE REVISED CALCULATIONS? 29. SEE PRIOR COMMENT #41. WHERE ARE REVISED CALCS? 30. SEE PRIOR COMMENT #42. WHERE ARE REVISED CALCS? 31. SEE PRIOR COMMENT #43. 32. SEE PRIOR COMMENT #45. 33. SEE PRIOR COMMENT #46. 34. SEE PRIOR COMMENT #47. 35. SEE PRIOR COMMENT #48. WHERE? 36. SEE PRIOR COMMENT #49. WHERE? 37. SEE PRIOR COMMENT #50. WHERE? 38. SEE PRIOR COMMENT #52. WHERE? 39. SEE PRIOR COMMENT #53. WHERE ARE HOLD-DOWN DETAILS ON DRAWINGS? 40. SEE PRIOR COMMENT #54. 41. SEE PRIOR COMMENT #55. 42. SEE PRIOR COMMENT #56. 43. SEE PRIOR COMMENT #57. 44. SEE PRIOR COMMENT #58. WHERE ARE CALCULATIONS? WHERE ARE DETAILS ON DRAWINGS? PRIOR COMMENTS ATTACHED.
02/02/2001 TGRIFFUS WATER REVIEW Approved
02/02/2001 ANY WWM REVIEW Stopped
12/22/2000 PATRICIA GEHLEN ZONING REVIEW Denied
12/28/2000 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied 1) The plan is unacceptable as submitted. The plan must be redrawn with all necessary corrections.
2) In accordance with the State Board of Technical Registration and the 1994 Uniform Administrative Code Modifications page 11, Section 302.2.1, 4. (4). an Electrical Engineer Registered in Arizona will be required to prepare and seal the document.
Please note I am retaining the electrical drawing in the event the State Board of Technical Registration requires a copy for review.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/12/2000 ANY APPROVAL SHELF Stopped
10/12/2000 ANY OUT TO CUSTOMER Stopped
10/12/2000 ANY REJECT SHELF Stopped