10/04/2022 JPEELDA1 COT NON-DSD FIRE Reqs Change Plans shall show the location of the FDC's, the F.D.C. shall be located on the street side in compliance with IFC 2018, Chapter 9, Section 912.2.1
Buildings greater than 30’ require aerial access to the building be provided IFC 2018, Appendix D 26’ wide drive and 15-30' from the building unobstructed. Areas noted as fire department aerial access shall also be on the plans with a note that reads: Fire Department Aerial access, no trees, canopies, solar shades or other obstructions shall ever be installed/planted in this area.