Plan Number: T22PRE0231
Parcel: Unknown

Address:
1056 N 9TH AV

Review Status: Active

Review Details: PREAPPLICATION LABELS

Plan Number - T22PRE0231
Review Name: PREAPPLICATION LABELS
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2022 ANY COT NON-DSD TRAFFIC Active
09/27/2022 ANY ZONING REVIEW Active
09/27/2022 ANY LANDSCAPE REVIEW Active
09/27/2022 ANY TUCSON WATER NEW AREA DEVELOPMENT REVIEW Active
09/27/2022 ANY ENGINEERING REVIEW Active
10/04/2022 JPEELDA1 COT NON-DSD FIRE Reqs Change Plans shall show the location of the new and existing fire hydrants
Plans shall show the location of the FDC's, the F.D.C. shall be located on the street side in compliance with IFC 2018, Chapter 9, Section 912.2.1
Buildings with Standpipes shall have a fire hydrant within 100' of the connections
Buildings greater than 30’ require aerial access to the building be provided IFC 2018, Appendix D 26’ wide drive and 15-30' from the building unobstructed. There are a lot of power lines that shall be relocated as both buildings will require the aerial access.
Will the building be classified as a high-rise, if so we will need more communication regarding High-Rise requirements.

Questions:

Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
Tucson Fire Department