Plan Review Detail
Review Status: Active
Review Details: PREAPPLICATION LABELS
Plan Number - T22PRE0231
Review Name: PREAPPLICATION LABELS
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/27/2022 | ANY | ZONING | REVIEW | Active | |
| 09/27/2022 | ANY | COT NON-DSD | TRAFFIC | Active | |
| 09/27/2022 | ANY | LANDSCAPE | REVIEW | Active | |
| 09/27/2022 | ANY | ENGINEERING | REVIEW | Active | |
| 09/27/2022 | ANY | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Active | |
| 10/04/2022 | JPEELDA1 | COT NON-DSD | FIRE | Reqs Change | Plans shall show the location of the new and existing fire hydrants Plans shall show the location of the FDC's, the F.D.C. shall be located on the street side in compliance with IFC 2018, Chapter 9, Section 912.2.1 Buildings with Standpipes shall have a fire hydrant within 100' of the connections Buildings greater than 30’ require aerial access to the building be provided IFC 2018, Appendix D 26’ wide drive and 15-30' from the building unobstructed. There are a lot of power lines that shall be relocated as both buildings will require the aerial access. Will the building be classified as a high-rise, if so we will need more communication regarding High-Rise requirements. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner Tucson Fire Department |