Plan Number: T22PRE0225
Parcel: Unknown

Address:
725 S 6TH AV

Review Status: Active

Review Details: PREAPPLICATION LABELS

Plan Number - T22PRE0225
Review Name: PREAPPLICATION LABELS
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2022 ANY ENGINEERING REVIEW Active 1. Ensure ES maneuverability to and from waste enclosure per TSM8-01.5.3. Waste enclosure must have 14'x40' operational area in front for waste collection, and ES trucks must not need to back up more than 80' in order to leave the property. Ensure that there is adequate room for ES trucks to turn around or that they can leave through the alley.
2. Ensure that refuse enclosure meets requirements per TSM 8-01.5.2 (10'x10' between bollards, 12' opening, concrete service apron)
3. Ensure 60' adequate driveway throat length with regard to parking adjacent to MS&R (Transportation Management Access Guidelines. 5.11) A waiver from DTM will be required to lower that requirement
4. Ensure that vehicle stops are sufficiently offset to prevent vehicle encroachment into sidewalk area. 4' minimum width must be maintained
5. Ensure vehicle overhang onto tree landscaping area will not force vehicles to encroach into PAAL.
6. Ensure that adequate area for vehicle maneuvering is present on the West parking spaces. Vehicles must not have to encroach into pedestrian walkways to exit parking spaces.

Lianne Evans
lianne.evans@tucsonaz.gov
09/29/2022 JPEELDA1 COT NON-DSD FIRE Completed Questions:

Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
Tucson Fire Department
10/12/2022 FRANK PODGORSKI HPZ ADVISORY BOARD HPZ ADVISORY BOARD DATE Active
10/18/2022 DSTIFFE1 COT NON-DSD TRAFFIC Reqs Change T22PRE0225
Comments:
1. Existing curb, sidewalk and the driveway apron on 6th Ave may remain. If impacting these items with construction, they will have to be constructed to meet current standards.
2. Where adjoining sidewalk from the property ties to sidewalk along the ROW frontage, a 60" X 60" ADA landing is required. Landings shall be 60" X 60" and not to exceed a 2% cross slope in all directions.
3. Radius for new curb return for the "Right Out" onto Arizona Ave must have a minimum radius of 12'.
4. Any new sidewalk along 6th Ave must be 6' wide.
5. Any new sidewalk along Arizona Ave must be 5' wide.
6. Any new concrete curb per P.A.G. standard 209.
7. Any new curb access ramps shall be constructed per P.A.G. standard 207.
8. For additional information contact an inspector for an onsite precon. 520-791-5100

David Stiffey
DTM Project Coordinator
David.Stiffey@tucsonaz.gov
10/19/2022 LSHAMIS1 ZONING REVIEW Completed CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review

FROM: Loran Shamis; Lead Planner

PROJECT: Thursday Pre-submittal meeting - T22PRE0225 - Wanslee Auto Restriping (related to DP21-0231)
Address: 725 S 6th Av
Parcel(s): 117-07-222A
Zoning: HC-3
Existing Use: Wanslee Auto Repair
Proposed Use: Administrative and Professional Office

TRANSMITTAL DATE: October 20, 2022

COMMENTS:

1. Development must comply with the Administrative Manual Section 2-06 - Development Package.

2. The site is zoned HC-3 and the proposed use is administrative and professional office is permitted.

3. The site is within a Historic Preservation Zone (HPZ) and requires review and approval from the Historic Preservation Office, contact Jodie Brown (Jodie.Brown@tucsonaz.gov) for more information.

4. The parking ratio for administrative and professional office is 1 space to 300 square feet of gross floor area. The parking ratio for commercial storage is 1 space per 5,000 square feet of gross floor area. Additionally, ensure the site is providing the enought parking to accomodate the use and the parking per the shared parking agreements with parcels 117-07-226B, 117-07-203A, and 117-07-205A.

5. Per the Shared Parking Agreement (T22SA00204), 16 parking spaces shall be reserved to meeting the minimum parking requirement for the Ugly but Honest Pizza site (117-07-205A).

6. Per the Refuse Agreement (T22SA00204) Ugly but Honest Pizza site (117-07-205A) is allowed to transfer solid waste refuge and recyclable waste to the subject site (117-07-222A).

7. Ensure the aisle width complies with the standards in UDC 7.4.6.D relative to the angle of the parking proposed.

8. Ensure pedestrian circulation is provided to the trash enclosure per Technical Standards Manual 7-01.

9. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions, please contact me at Loran.Shamis@tucsonaz.gov.
10/20/2022 JCARLTO1 LANDSCAPE REVIEW Completed Landscape has no comments.

Matthew Carlton
Matthew.Carlton@tucsonaz.gov
10/20/2022 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Completed 130 - 200 pm - T22PRE0225 - 725 S 6TH AV
Site Wanslee Auto - HC-3 zoning

Completed

1. Tucson Water's New Area Development Unit has no objections to the proposed re-striping of the parking lot.

2. The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
201 N. Stone Avenue, #2-220
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106