Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Plan Number: T22PRE0196
Parcel: Unknown

Review Status: Active

Review Details: PREAPPLICATION MEETING

Plan Number - T22PRE0196
Review Name: PREAPPLICATION MEETING
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/06/2022 JOHN BEALL M&C Public Hearing 4 Plan Amendment Set M&C Public Hearing Date Active
09/06/2022 BILLIE LEE COMMENTS COMMENTS Active
09/06/2022 JPEELDA1 FIRE REVIEW Reqs Change Buildings exceeding 30’ shall be provided with aerial access meeting IFC 2018, Appendix D, Section D105. D105.3 Proximity to building. One or more of the required access routes meeting this condition shall be located not less than 15’ and not greater than 30’ from the building, and shall be positioned parallel to one entire side of the building. The side of the building on which aerial apparatus access road positioned shall be approved by the fire code official.

Fire hydrants shall be located within 400 ft of new structures. IFC 2018, Chapter 5, Section 507.5.1 and also in accordance with IFC Appendix D. Please show new and existing fire hydrant locations on the plans and or fire sprinklers shall be installed.

TFD requires that gates across an apparatus access road be 20’ wide and if powered have a KNOX Gate key switch and KNOX Box located at the gate. This note shall be added to your drawings.

Apparatus access roads shall be within 150’ of all portions of a building. IFC 2018, Chapter 5, Section 503.1.1

Questions:

Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
09/07/2022 NMARTEL1 ZONING REVIEW Completed Rezoning Pre-Submittal Transmittal

FROM: Nick Martell
PDSD Zoning Review

PROJECT: Rezoning Pre-submittal meeting T22PRE0196
Address: 3801 N Campbell
Parcel(s): 11301010C, 11301018C, 11301017C
Existing Zoning: R-1, O-3
Proposed Zoning: R-3
Existing Use: Commercial-Administrative and Professional Office
Proposed Use: Residential-Multifamily Residential

TRANSMITTAL DATE: September 7, 2022

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. Proposed use and use-specific standards:4.9.7.B.6-Manufactured Housing is not Considered a Dwelling Unit
3. Development standards: 40 ft building height
4. Perimeter yard setbacks: Adjacent to R-1, O-3 and MH-1 zones = 10' or 2/3 (H)
5. Applicable street setbacks: Campbell and Allen are both subject to MS&R setbacks of 21' or H from the back of the existing or future curb.
6. Parking requirements: See UDC Article 7.4.4 https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-5445
7. Bike parking requirements: See UDC Article 7.4.8 https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-5698
8. Landscape requirements can be discussed further with Anne Warner at Anne.Warner@tucsonaz.gov
9. Additional comments:
a. Any demolition of structures greater than 50 years old will require archeological documentation and historic review
b. A lot combo may be required
10. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions, please contact me at nicholas.martell@tucsonaz.gov.
09/07/2022 LOREN MAKUS ELECTRICAL ENGINEERING REVIEW Completed 1. Site is in a balanced basin. Engineering will request critical basin detention.
2. Low impact development design will be required.