08/03/2022 | JPEELDA1 | COT NON-DSD | FIRE | Completed | Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner |
08/10/2022 | IMONSHI1 | ZONING | REVIEW | Completed | FROM: Iman Monshizadeh PDSD Zoning Review Section PROJECT: T22PRE0172 (1402 W Ajo Wy – Mesa Ridge MHC) TRANSMITTAL DATE: 8/9/2022 A development package will be required for this site. Information on the development package can be found at: https://www.tucsonaz.gov/files/pdsd/forms/Development_Package_and_Land_Division-Subdivision_Application.pd Submittal Requirments: https://www.tucsonaz.gov/files/pdsd/forms/Submittal_Requirements.pdf Could not find much information on the total number of approved MH on this lot however historic permit number H000012394 may provide some information that might help (dated 1962) Setbacks for the rear and side yard in an MH-1 zone are 6’ or 2/3 * Height (whichever is greater). Setbacks are measured from structure to property line. Density calculations for the MH-1 Zone are 8 units per acre, with a maximum lot coverage of 70% The portion of the lot that is being developed will need to be code compliant. If the additions are greater than 25% gross floor area of the entire site, then the entire site will be required to be brought up to code. If you can provide documentation showing that areas were previously approved as buildable then those areas will not count towards that expansion percentage. For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov / (520) 837-4082 |
08/10/2022 | AWARNER1 | LANDSCAPE | REVIEW | Passed | |
08/10/2022 | SCABRAL1 | ENGINEERING | REVIEW | Completed | 1. Maximize water harvesting in any new landscaping. 2. Make sure to address existing water courses that run through Holiday PL, Holiday Isle BL, and Holiday PZ into Holiday AV and how they will be maintained. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
08/10/2022 | SBEASLE1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Completed | 300 - 330 pm - T22PRE0172 - 1402 W AJO WY Site: Mesa Ridge 1. Tucson Water's New Area Development Unit has no objections to the proposed new development and offers the following comments for your convenience. 2. The majority of the existing Mesa Ridge development is served by an on-site private water distribution system connected to an existing 4" master water meter that measures water obtained from a 12" water main in Tucson Water's existing distribution system. 3. The area of the proposed development is served by the on-site private water distribution system. This area is not directly served by Tucson Water. Tucson Water is unable to comment on the capacity of the on-site private water distribution system to serve the proposed new development. 4. Tucson Water's existing distribution system has the capacity necessary to serve the proposed new development. Should there be a capacity issue associated with the existing 4" master water meter, the owner/developer of the project may have it replaced with a larger or different type of water meter at his or her own expense, by contacting Tucson Water's New Services section by sending an e-mail to TW_Common@tucsonaz.gov. 5. The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to: Tim Rowe, P.E., Civil Engineer Tucson Water, New Development Section 201 N. Stone Avenue, #2-220 P.O. Box 27210 Tucson, AZ 85726-7210 (520) 837-2106 tim.rowe@tucsonaz.gov |
08/15/2022 | DSTIFFE1 | COT NON-DSD | TRAFFIC | Completed | No Comments |