Plan Number: T22PRE0116
Parcel: Unknown

Review Status: Active

Review Details: PREAPPLICATION MEETING

Plan Number - T22PRE0116
Review Name: PREAPPLICATION MEETING
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2022 JPEELDA1 FIRE REVIEW Completed 2018 International Fire Code
Building shall comply with IFC 2018, Section 507.5 or fire sprinklers shall be installed. Provide diagram on plans of hose lay as the hose lays not the crow flies on your Development Plan.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@tucsonaz.gov
520-837-7033
Fire Plans Examiner
06/07/2022 JOHN BEALL M&C Public Hearing 4 Plan Amendment Set M&C Public Hearing Date Active
06/07/2022 ANY ELECTRICAL ENGINEERING REVIEW Active
06/07/2022 BILLIE LEE COMMENTS COMMENTS Active
06/16/2022 NMARTEL1 ZONING REVIEW Completed PDSD Zoning Review
FROM: Nicholas Martell, Planner
Parcel(s): 135020220
Zoning: C-1
Existing Use: Retail-General Merchandise Sales
Proposed Use: Commercial-Automotive Minor Service and Repair
1. The proposed use for the Drive-thru oil change shop is Commercial-Automotive-Minor Service and Repair. It is only permittable through the Zoning Examiner Special Exception Procedure per 3.4.3 of the UDC. The development is subject to use specific standards 4.9.4.F.2, .3, .4, & .5 and 4.9.13.O
2. Archeological documentation is required for the demolition of structures greater than 50 years old.
3. . E 22nd street and Avenida Polar are both subject to Major Street and Route setbacks of 21' from the back of the existing or future curb. 22nd appears fully built out.
4. Ensure ADA width requirements of 16' are met.
5. Ensure access standards found in section 7.8 of the UDC and sections 7-01.0.0 and 10-01.0.0 of the Technical Standards Manual are met. Pedestrian access along the street is required. Show complete pedestrian circulation for the site.

If you have any questions, please contact me at Nicholas.Martell@tucsonaz.gov