Plan Number: T22PRE0105
Parcel: Unknown

Review Status: Completed

Review Details: PREAPPLICATION LABELS

Plan Number - T22PRE0105
Review Name: PREAPPLICATION LABELS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2022 AWARNER1 LANDSCAPE REVIEW Passed
05/24/2022 JPEELDA1 COT NON-DSD FIRE Completed Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@tucsonaz.gov
520-837-7033Fire Plans Examiner
05/25/2022 PAUL CAMARENA ZONING REVIEW Completed CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review
FROM: Paul Camarena, Planner
PROJECT: Thursday Pre-submittal meeting – T22PRE0105
Address: 1231 N Belvedere AV
Parcel(s): 122120640
Zoning: R-2
TRANSMITTAL DATE: 05/24/2022

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-07 - Block Plat
2. Provide a complete legal description of the property.
4.Tucson Water requires 15' of street frontage per new lot which cannot be satisfied with an easement. Demonstrate the existing structures will comply with the required minimum setbacks with the new parcel line to accommodate this Tucson Water requirement.
5. Provide the heights of the building in order to verify the setback requirements
6. The minimum lot size is 5,000 SF
7. The setbacks are 6' or 2/3(height) greater of the two.
8.The maximum height is 25'
9. Show everything on-site there are two sheds clarify if theses are to be removed.


If you have any questions, please contact me at Paul.Camarena@tucsonaz.gov
05/25/2022 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Denied 200 - 230 pm - T22PRE0105 - 1231 N BELVEDERE
Block Plat, 1231 and 1235 N. Belvedere Rd

1. Tucson Water's Remote Meter Policy prohibits the private water service line for Lot 1 to lie within a private easement on Lot 2.

2. To comply with Tucson Water's remoted meter policy, one of the following must occur:
A. Lot 1 be re-configured as a 'flagpole' lot, so that it will have a minimum of 15' of real property frontage on Belvedere. The private water service line serving Lot 1 would then lie completely within Lot 1, and the existing water meter for both Lot 1 and Lot 2 could remain where they are. Lot 2 would be smaller, but no access/egress or utility easements across Lot 2 would be needed.
B. If the owner/developer of APN 122120640 wishes to split this lot as proposed in the submitted drawings, he or she would need to:
i. Grant the proposed 15' private access/egress easement on Lot 2 to all future owners of Lot 1
ii. Grant a 15' public water easement over the proposed 15' private access/egress easement on Lot 2 to the City of Tucson
iii. Remove the existing water meter and private water service line currently serving the 1235 residence.
iv. Construct a new 4" public water main within the 15' public water easement on Lot 2 from the public water main in Belvedere to the eastern edge of Lot 1, and
v. Relocate the water meter for the 1235 residence to the eastern edge of Lot 1 (i.e. the west end of the new 4" water main).

3. The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
201 N. Stone Avenue, #2-220
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
tim.rowe@tucsonaz.gov
05/25/2022 SBLOOD1 ENGINEERING REVIEW Completed 1. General notes as applicable and standard paragraphs need to be included on the plat as per Admin Manual 2-07.5.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
05/26/2022 DSTIFFE1 COT NON-DSD TRAFFIC Approved Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@tucsonaz.gov
520-837-7033Fire Plans Examiner