| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2022 | JPEELDA1 | COT NON-DSD | FIRE | Completed | Plans shall show the existing fire hydrant locations. Hydrants shall meet the 2018 IFC, Section 507.5, 507.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 400 ft from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided exception: building that have fire sprinklers are allowed 600'. If there are hydrants within the 400' we shall verify the required fire flow from Tucson Water prior to approval of structure without fire sprinklers. Gates across a fire department access lane shall conform to IFC 2018, Section 503.2 & Section 503.6. Plans shall show the use of a KNOX Gate key switch if electric gates are installed across the access road. Provide a life safety sheet Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner |
| 03/22/2022 | SBEASLE1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Passed | For any water related questions, please contact Mr. Michael Mourreale at Michael.Mourreale@TucsonAz.gov. Tim Rowe, P.E., Civil Engineer Tucson Water, New Area Development Unit |
| 03/22/2022 | DSTIFFE1 | COT NON-DSD | TRAFFIC | Completed | T22PRE0047 Comments: 1. New 5 Ft wide sidewalk along the entire property frontage 2. New curb returns- 18 Ft. radius 3. New concrete curb per P.A.G. standard 209 (Existing curb is wedge curb) 4. New curb access ramps per P.A.G. standard 207 5. At least one sidewalk is required from each street on which the project has frontage, connecting the property to the ROW 6. Sidewalks are required adjacent and parallel to any access or PAAL lane 7. Where adjoining sidewalk from the property ties to sidewalk along the ROW frontage, a 60" X 60" ADA landing is required (this at curb returns or a type 1 curb access ramp) (60" X 6" Landing not to exceed 2% cross slope in all directions.) 8. 3' minimum buffer between curb and sidewalk, unless ROW is limited David Stiffey DTM Project Coordinator David.Stiffey@tucsonaz.gov |
| 03/23/2022 | IMONSHI1 | ZONING | REVIEW | Completed | FROM: Iman Monshizadeh PDSD Zoning Review Section PROJECT: T22PRE0042 (3801 N Runway– U-Haul Warehouse) TRANSMITTAL DATE: 3/23/2022 1.COMMENT: This project will require a development package, Information on the Development package can be found at. https://www.tucsonaz.gov/files/pdsd/forms/Development_Package_and_Land_Division-Subdivision_Application.pd 2.COMMENT: Both commercial storage and personal storage are permitted in the I-1 zone. The use specific standard for the uses in this zone are Commercial Storage: 4.9.10.A and 4.9.13.Q Personal Storage: 4.9.10.C.3 & .6 and 4.9.13.Q 3.COMMENT: If site is used to store materials for U-haul's business use then the use will be considered commercial storage. If site is open to public to store personal items, it will be personal storage. If site is considered personal storage without vehicle access, then 5 parking spaces will be required For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp |
| 03/23/2022 | AWARNER1 | LANDSCAPE | REVIEW | Completed | CDRC TRANSMITTAL PROJECT: UHC of So. Arizona ACTIVITY NO. T22PRE0047 ADDRESS/PARCEL: 3801 N Runway Dr ZONING: I-1 7.6 Landscaping and Screening The Unified Development Code (UDC) requires all new development or an expansion of greater than 25% of an existing development submit a landscape plan, UDC 7.6.2. Preparation of the landscape plan shall adhere to UDC 7.6.4. and Administrative Manual 2-10. • 10’ street landscape border required along Runway and Highway Drives. Placing trees along the edge of a parking area or at the ends of parking row does not meet the intent of the UDC. All spaces within 40’ of a tree is only one of the requirements. The intent is to provide as much shade on the asphalt as possible, and the requirement is 1 tree per 4 parking spaces; trees are expected to be placed within the parking area itself to provide shade on asphalt. Trees are to be distributed evenly throughout the parking area, UDC 7.6.4.1.B.1, UDC Technical Standards Manual 5-01-.3.2 and UDC 7.6.4.B.1.a. Commercial Rainwater Harvesting plan is required UDC Technical Standards Manual – Section 4-01.0.0. and Section 5-01.0.0 Landscaping and Screening Adherence to the Low Impact Development Standards outlined in Section 5 of the PCRFCD Design Standards for Stormwater Detention and Retention is required and shall work in conjunction with the Commercial Rainwater Harvesting design. Using Low Impact Development design and water harvesting provides critical basin detention and first flush retention for all new development and impervious area. The newly adopted Detention/Retention Manual can be found: https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Flood%20Control/Rules%20and%20Procedures/Stormwater%20Detention-Retention/dssdr-final-201406-manual.pdf With CoT edits to the manual are found at: https://www.tucsonaz.gov/files/pdsd/codes/Detention_Retention_Manual_Tech_Standards_Amemdments.pdf If you have any questions about this transmittal, contact Anne Warner, RLA PDSD Landscape/NPPO Review at email anne.warner@tucsonaz.gov |
| 03/24/2022 | SBLOOD1 | ENGINEERING | REVIEW | Completed | 1. The site is in a critical basin. Critical basin detention and first flush retention are required for the entire site since this is more than a 25% expansion. 2. Maximize water harvesting in new landscape areas. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |