Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: T22PRE0028
Parcel: Unknown

Review Status: Completed

Review Details: PREAPPLICATION LABELS

Plan Number - T22PRE0028
Review Name: PREAPPLICATION LABELS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2022 LSHAMIS1 ZONING REVIEW Completed CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review

FROM: Loran Shamis; Planner, MBA

PROJECT: Thursday Pre-submittal meeting - T22PRE0028
Address: 10129 E Speedway Bl
Parcel(s): 13303315H
Zoning: SR
Existing Use: Educational
Proposed Use: Educational and Day Care

TRANSMITTAL DATE: February 24, 2022

COMMENTS:

1. Development must comply with the following Checklist for Minor Development Changes to Existing Commercial/Industrail Sites - https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf.

A Zoning Examiner Special Exception Procedure is required. The applications for the DP and the ZE Special Exception Procedure can be processed concurrently, however, Zoning cannot approve the DP prior to approval or the ZE Special Exception.

2. The proposed use is Civic Use Elementary and Secondary which is permitted in the SR zone, subject to use specific standards 4.9.3.D (table 4.8-1).

3. Commercial Use Day Care with Unlimited Maximum of Children requires a Zoning Examiner Special Exception Procedure, subject to use specific standards 4.9.4.H.1-5, .7.f, & .8 (t5able 4.8-1).

4.9.4.H.5 - Min. distance of outdoor recreation areas, includig, but not limited to, swimming and wading pools, ball fields, and playground equipment, to any adjacent property in R-3 or more restrictive zoning shall be 25'. Where abutting a street or alley, the setback shall be measured to the centerline or a right-of-way. A wall shall be required between a recreation area provided on site and adjacent to R-3 or more restrictive zoning.

4. If the bicycle and vehicle parking requirement for the portion of the site used for the Day Care Use exceeds the parking requirement for the use it is replacing (Educational Use), then parking dedicated to the proposed use (Day Care) must be compliant with UDC 7.4.

5. The minimum required vehicle parking ratio for Educational Use Grades K - 8 is 1 space per 10 students plus 1 space per 300 sq ft of floor area in office use (Table 7.4.4-1).

6. The minimum required vehicle parking ratio for Day Care Use is 1 space per 300 sq ft of gross floor area (GFA). (Table 7.4.4-1).

7.The minimum required bicycle parking ratio for Educational Use Grades K-12 is 1 short-term bicycle space per 20 students of planned capacity, and 1 long-term space per 10 employees plus 1 space per 20 students of planned capacity (Table 7.4.4-1).

8. The minimum required bicycle parking ratio for Day Care is 1 short-term space per 40,000 sq ft of GFA and 1 long-term space per 12,000 sq ft GFA (table 7.4.8-1).

9.The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions, please contact me at Loran.Shamis@tucsonaz.gov.
02/23/2022 AWARNER1 LANDSCAPE REVIEW Completed
02/23/2022 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Completed 300 - 330 pm - T22PRE0028 - 10129 E SPEEDWAY BL - Site Higher Ground Education

1. Tucson Water's New Area Development Unit has no objections to the proposed development and offers the following comments for your convenience.

2. The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
201 N. Stone Avenue, #2-220
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
tim.rowe@tucsonaz.gov
02/24/2022 NROSS1 COT NON-DSD TRAFFIC Completed 1. Any non-compliant curb, sidewalk, curb access ramps to be brought up to standard.
02/24/2022 SBLOOD1 ENGINEERING REVIEW Completed 1. Show that the proposed work doesn't affect the existing LOMA excluding the structure from the floodplain.
2. Maximize water harvesting in any new landscaping.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
02/24/2022 MROSS2 COT NON-DSD FIRE Completed Automatic Sprinkler Systems
903.2 Where required.
Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Sections 903.2.1 through 903.2.12.

Fire Alarm and Detection Systems
907.2 Where required-new buildings and structures. An approved fire alarm system installed in accordance with the provisions of this code and NFPA 72 shall be provided in new buildings and structures in accordance with Sections 907.2.1 through 907.2.23 and provide occupant notification in accordance with Section 907.5, unless other requirements are provided by another section of this code.

FIRE HYDRANTS
507.5.1 Where required.

Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 400 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.

Exceptions:

1. For Group R-3 and Group U occupancies, the distance requirement shall be 600 ft.

2. For buildings equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, the distance requirement shall be 600 feet.


Michael Ross
Tucson Fire Department
520-837-7082
Michael.Ross2@tucsonaz.gov