Permit Number: T22OT00350
Parcel: 12713078B

Review Status: Completed

Review Details: C OF O

Permit Number - T22OT00350
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G-1; Code Review: The Code indicates the 2000 IBC. Please revise.
2. Sheet G-1; Code Review: The Use indicates Office TI. Please revise.
3. Sheet G-1; Code Review: The Occupancy indicates B. Please revise.
4. Sheet G-1; Code Review: The Occupant Load indicates 24. PLease revise.
5. Sheet G-1; Index to Drawings: Please revise for this project Certificate of Occupancy.
6. Sheet G-1; Stamp: Please revise the stamp. The current architect must seal, sign, and date the drawings for this change of use.
7. Sheet A-1: This sheet is not needed for the Certificate of Occupancy application.
8. General: Please provide written responses to all review comments.
06/15/2022 STEVE SHIELDS ZONING REVIEW Approved