Permit Review Detail
Review Status: Completed
Review Details: C OF O
Permit Number - T22OT00350
Review Name: C OF O
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G-1; Code Review: The Code indicates the 2000 IBC. Please revise. 2. Sheet G-1; Code Review: The Use indicates Office TI. Please revise. 3. Sheet G-1; Code Review: The Occupancy indicates B. Please revise. 4. Sheet G-1; Code Review: The Occupant Load indicates 24. PLease revise. 5. Sheet G-1; Index to Drawings: Please revise for this project Certificate of Occupancy. 6. Sheet G-1; Stamp: Please revise the stamp. The current architect must seal, sign, and date the drawings for this change of use. 7. Sheet A-1: This sheet is not needed for the Certificate of Occupancy application. 8. General: Please provide written responses to all review comments. |
| 06/15/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved |