Permit Review Detail
Review Status: Completed
Review Details: C OF O
Permit Number - T22OT00316
Review Name: C OF O
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/23/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22OT00316 2502 N Dodge Bl – O-3 C of O (1st Review) TRANSMITTAL: May 23, 2022 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the O-3 zone (UDC 4.7.15). 1. The provided vehicle parking space calculation is not correct, vehicle parking is not based on occupancy. Provide a vehicle parking calculation based on uses as defined within the UDC. 2. Provide a use as defined within the UDC for the proposed occupancy. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
| 05/23/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet g1.2; Code Analysis: Please provide the total building square footage and occupant load for the south building on this sheet. 2. Sheet g1.2; Code Analysis: Please indicate the Construction Type of the south building on this sheet. 3. General: Please clarify on these documents that this C of O is for the south building only. 4. General: Please provide written responses to all review comments. |