Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review


PROJECT:
T22OT00265
345 E Teton Rd - R-2
C of O for Physical and Behavioral Health Service (1st Review)

TRANSMITTAL: April 22, 2022
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-2 zone (UDC 4.7.9). Physical and Behavioral Health Service – Limited to 10 Residents is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.J. 2.a, 3.a, 4.

1. As you are proposing a change of use per UDC Article 3.3.3.G.2.c and proposing more than 4 vehicle parking spaces a development package meeting the requirements of AM 2-06 is required to be submitted and approved prior to this C of O.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/05/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-1; 'This Project Description': This indicates the new group home is to be located in Existing Building #2. Should this be #3? Please verify.
2. General: Information for the Construction Type was not located on the drawings. In addition, per the IBC Section 420.4, Group R occupancies shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.2.8. Please verify.
3. General: Please provide written responses to all review comments.