Review Status: Completed
Review Details: C OF O
Permit Number - T22OT00187
Review Name: C OF O
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/01/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/01/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: If the intent of this permit is to obtain a Certificate of Occupancy for the portion of the building denoted in red on the Floor Plan, a registered architect must produce a floor plan and Code Analysis, indicating the Occupancy Classification, square footage of the space, Construction Type, sprinkler system, and Occupant Load. It appears the space received a Letter of Completion in a 2015 project, indicating the space originally had a Certificate of Occupancy for a business (B) occupancy classification. Therefore, a new Certificate of Occupancy would not be necessarily required since there was no change of use. Please verify and include a project narrative on the new floor plan. |