Permit Number: T22OT00122
Parcel: 133086320

Address:
8240 E KEUKA CT

Review Status: Completed

Review Details: C OF O

Permit Number - T22OT00122
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G1 (Code Check); Sheet A1 (Floor Plan): The Code Check indicates this is an R-1 with 20 occupants. The Floor Plan indicates 5 bedrooms with 8 beds. The occupant load should be based on the bedroom sizes and capacities. Use 80 SF for one occupant in a bedroom, and 120 SF for two occupants in a bedroom to determine the total occupant load. As indicated on the Floor Plan, it would be 8 occupants. This would change the Occupancy Classification to an R-4. Please verify.
2. Sheet A1; Floor Plan: Please verify and indicate on the drawings the requirements of Section 305.8.10 of the 2018 IEBC are met for accessible restrooms provided.
3. General: Please provide written responses to all review comments.
03/17/2022 STEVE SHIELDS ZONING REVIEW Approved