Permit Number - T22OT00118
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Code Review (Plumbing Requirements): Item 7 indicates "15 or less drinking fountain not required". The occupant load is 20, and the IBC Section 2902.6 requires a drinking fountain. Please revise.
2. General: Please provide written responses to all review comments.
03/14/2022 LSHAMIS1 ZONING REVIEW Reqs Change CDRC Transmittal

FROM: Loran Shamis
PDSD Zoning Review Section

PROJECT: T22OT00118
Certificate of Occupancy (1st Review)
1502 E 20th St

TRANSMITTAL DATE: March 14, 2022

DUE DATE: March 16, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

01. COMMENT: It appears the site qualifies for improvement relief per UDC 3.3.3.H, Zoning Compliance for Site Improvements in Existence on May 1, 2005 - https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-841.

02. COMMENT: Per 3.3.3.H.9, the owner of the property shall submit the following:
a. A sworn affidavit that the use of the property will be in compliance with UDC 3.3.3.H - https://www.tucsonaz.gov/files/pdsd/forms/C_of_O_Releif_Affidavit.pdf
b. Include the following in any lease/rental agreement for the property: "Tenant shall not cause or permit the Property to be used in any way which constitutes a violation of any law, ordinance, or governmental regulation. Notwithstanding any contrary provision of this lease agreement, any occupancy or use of the premises in violation of this paragraph constitutes a material breach of this lease agreement entitling Lessor to invoke all remedies provided hereunder including termination."

For questions regarding Zoning comments, please contact me at: Loran.Shamis@tucsonaz.gov
To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp