Permit Number: T22OT00075
Parcel: 137051950

Address:
731 W NEVADA ST

Review Status: Completed

Review Details: C OF O

Permit Number - T22OT00075
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Building Code Analysis: Sprinklers are indicated on this sheet as "Not required 2018 IEBC Sect. 703". Chapter 10 should be used as the guidelines for a change of occupancy. Per the IEBC Section 1004, and automatic sprinkler system is required using the IBC Chapter 9 requirements, and the requirements of the IEBC Section 1011. Please verify and revise.
03/07/2022 STEVE SHIELDS ZONING REVIEW Approved