Permit Number: T22MH00054
Parcel: 138234890

Review Status: Completed

Review Details: MOBILE HOME

Permit Number - T22MH00054
Review Name: MOBILE HOME
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2022 AWARNER1 NPPO REVIEW Approved
08/29/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
08/30/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/12/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review Section

PROJECT:
T22CM06789
703 W Lightstar Ci. – R-1
Manufactured Home (1st Review)

TRANSMITTAL: September 12, 2022

COMMENT: Resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 5.10.3). A Manufactured Home is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 – 9

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf, to include the following:
a. The plot plan shall be drawn at an engineering scale, i.e. 1” = 10’, 1” = 20’ etc.
b. Provide the owners name on the plot plan.
c. Provide a dimension from the center line of the street east property line. The distance from center line to the property line should be 15’-0”.
d. The property dimensions are not correct. Review the Los Santos Reales final plat found at: https://gis.pima.gov/maps/subdiv/select.cfm?bkpg=50059&seqnum=, and provide the correct dimensions.
e. Indicated the zoning for this parcel and all adjacent parcels on the plot plan. The zoning should be R-1.
f. Per the final plat mentioned above there is an 8’-0” PPUE shown along the east property line. Show this easement on the plan.
g. Per the final plat mentioned above there is an 1’-0” NVAE shown along the west property line. Show this easement on the plan.

2. The provided plot plan shows the street running along the south property line and it should be along the east property line.

3. Provide a perimeter yard setback dimension from the proposed Manufactured Home to the east property line.

4. Provide the following notes on the plot plan: Per UDC Articles 4.9.7.B.5 – 6 the following apply:
a. A manufactured housing unit is not considered a dwelling for the purposes of this section, unless it is located in a subdivision recorded after January 1, 1982, and not located in a re-subdivision of any subdivision recorded prior to January 1, 1982.
b. A manufactured housing unit is not considered a dwelling for the purposes of this section, unless the following standards are met or a subdivision plat that has been clearly identified for manufactured housing has been approved and permits for manufactured homes have been issued for 25% or more of the lots prior to December 27, 2000:
c. It is placed on an excavated and backfilled foundation (ground set). If the home is located in a floodplain, the bottom of the lowest floor joist shall be a minimum of one foot above the 100-year/base flood elevation, and the foundation of the home shall be placed on the fill ;
d. No more than eight inches of perimeter skirting wall shall be visible from the street frontage of the property. The perimeter skirting wall shall match the exterior color of the home;
e. The exterior siding materials shall be either hardboard, vinyl, or stucco;
f. Concrete or masonry steps shall be provided for the entry on the street side of the dwelling;
g. All entry doors on the street side of the dwelling shall be inward-swinging doors; and,
h. The roofing style and materials shall be either flat roof (Pueblo), steel rib roof, or shingle or tile roof with a 3:12 roof pitch or greater. All pitched roofs, except those that are disguised by a parapet, shall have a minimum six inch eave on all sides of the dwelling.

5. Provide the following notes on the plot plan: Per UDC Article 11.3.7 definition of Manufactured Housing a multi-sectional mobile home dwelling manufactured after June 15, 1976, to standards established by the U.S. Department of Housing and Urban Development that has external dimensions of at least 24 feet by 40 feet and is installed on a permanent foundation. A manufactured housing unit is considered equivalent to a single-family dwelling. To be considered a manufactured housing unit under this UDC , a wall must be installed continuously, except for ventilation and access, along the entire perimeter of the unit between the unit and the ground to give it the appearance of a site -built house. The wall must be of masonry construction or similar material. The tongue, axles, transporting lights, and towing apparatus must be removed before occupancy.

6. The plot plan and calculation shall be submitted on a singe pdf file.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/15/2022 KROBLES1 WWM REVIEW Passed