10/19/2022 ANY ELECTRICAL-COMMERCIAL REVIEW Active
10/19/2022 ANY BUILDING-COMMERCIAL REVIEW Active
10/20/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. Reference: Section C503.4, IECC 2018.