Permit Review Detail
Review Status: Active
Review Details: OTHER
Permit Number - T22CM08049
Review Name: OTHER
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2022 | ANY | ELECTRICAL-COMMERCIAL | REVIEW | Active | |
| 10/19/2022 | ANY | BUILDING-COMMERCIAL | REVIEW | Active | |
| 10/20/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. Reference: Section C503.4, IECC 2018. |