Permit Number: T22CM07910
Parcel: 126090820

Address:
113 N DOUGLAS CI

Review Status: Active

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM07910
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2022 ANY BUILDING-RESIDENTIAL REVIEW Active
10/17/2022 JCARLTO1 NPPO REVIEW Passed
10/17/2022 SHASEMA1 ENGINEERING REVIEW Passed
10/20/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM07910
Addition
113 N DOUGLAS CI Zoning R-1

TRANSMITTAL DATE:?October 20, 2022


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: Revise the site plan scale to an engineering scale.

2.COMMENT: The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a scaled measurement the wall height is 13’-9” the required perimeter yard setback from the proposed SFR to the west property line is 9’-3”, proposed scaled setback is 5-0”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback,
DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov

2.COMMENT: Draw dimension and label the height of the new structure measured from design grade to top of wall. Provide all setback dimensions.

3.COMMENT: Clearly show everything on site. Additional comments may be forth coming.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov