Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM07639
Parcel: 136381830

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM07639
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2022 RPARSON1 OIP REVIEW Completed
10/18/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM07639

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1. Show the size and total number and spacing of lag bolts
2.Provide sufficient standoffs for achieving a point load calculation under 45 pounds, R301.1 Provide calculations.


BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/18/2022 VVERA1 OUT TO CUSTOMER Completed