Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM07633
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/05/2022 | RPARSON1 | OIP | REVIEW | Completed | |
10/18/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM07633 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Provide uplift calculations demonstrating sufficient anchorage for 115 mph windspeed given the exposure. 2. Demonstrate point load impact less than 45 lbs per support on roof. BUILDING REVIEW COMMENTS: Approved Installation of 16 modules and associated equipment on existing dwelling unit approved. MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Approved Installation of pv system with backfeed approved. PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/18/2022 | VVERA1 | OUT TO CUSTOMER | Completed |