Permit Number: T22CM07627
Parcel: 118200810

Address:
340 W 24TH ST

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM07627
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2022 RPARSON1 OIP REVIEW Completed
10/18/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM07627

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Please note adopted windspeed is 115 MPH for this jurisdiction. Provide wind load calculations demonstrating sufficient anchorage for uplift R301.1


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Denied
1. Please clarify labels with drawings. Showing line side taps yet labeling for backfeed breaker...

PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/18/2022 VVERA1 OUT TO CUSTOMER Completed