Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/04/2022 | GSLEIGH1 | OIP | REVIEW | Reqs Change | Gas line to most distal furnace is undersized, 1/2 inch at 56' provides only 65k BTU/hr, 100k required. The 13' 3/4" section is undersized, provides 199k BTU/hr, 200k required. |