Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM07582
Parcel: 115041940

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM07582
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2022 GSLEIGH1 OIP REVIEW Reqs Change Gas line to most distal furnace is undersized, 1/2 inch at 56' provides only 65k BTU/hr, 100k required. The 13' 3/4" section is undersized, provides 199k BTU/hr, 200k required.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2022 NGARCIA3 OUT TO CUSTOMER Completed