Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2022 ANY WATER REVIEW Active
09/30/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW RECEIVED
10/03/2022 SHASEMA1 ENGINEERING REVIEW Passed
10/04/2022 JPEELDA1 FIRE REVIEW Reqs Change Plans shall show the building has fire sprinklers, add note that fire sprinkler permits shall be obtained from TFD
Plans shall show if the building has a fire alarm system and if so add note like the fire sprinkler note
Kitchen fire suppression system plans shall be submitted to and a permit obtained from TFD
Provide an exiting plan
Plans shall show the occupant load on the cover sheet

Questions:

Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
Tucson Fire Department
10/19/2022 STEVE SHIELDS ZONING REVIEW Approved