Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Active
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM07522
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/30/2022 | ANY | BUILDING-RESIDENTIAL | REVIEW | Active | |
| 10/03/2022 | SHASEMA1 | ENGINEERING | REVIEW | Reqs Change | Project: T22CM07522 Address: 4439 E Seneca St This project is within a regulated floodplain and requires a Floodplain Use Permit (FUP.) Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. Instructions: 1. Is this for a new or existing activity application? – Please select New Application. 2. Submission Type – Select Floodplain Use Permit. 3. Project Name – Enter a name for your project. 4. Type of Permit – Select Commercial or Residential (Residential is for work on single family residences and duplexes.) 5. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided. 6. Description of Work – Enter in Floodplain Use Permit for…and then put a description of the work being done or reference the building permit number associated with this floodplain use permit. 7. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account. 8. Complete the Contractor, Owner and Architect/Engineer sections as applicable. 9. *IMPORTANT* Supporting Documentation Upload – Provide a complete cost estimate for the project unless it is for a new build/separate structure. You may also provide additional documents you think will be helpful. 10. Sign the application and submit. Contact Scott Haseman at scott.haseman@tucsonaz.gov, Stephen Blood at Stephen.Blood@tucsonaz.gov, or Loren Makus at Loren.Makus@tucsonaz.gov if you have any questions about the FUP. |
| 10/12/2022 | JCARLTO1 | NPPO | REVIEW | Passed | |
| 10/13/2022 | PAUL CAMARENA | ZONING | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: T22CM07522 New SFR 4439 E SENECA ST Zoning R-2 TRANSMITTAL DATE:?October 13, 2022 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1.COMMENT: Provide a Residential Plot Plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf This shall in include: a. Lot coverage calculation that meets the requirements of UDC Article 6.4.3 & the example shown on the residential plot requirements. (Lot coverage must include vehicular use area whether improved or unimproved) b. Zoning of adjacent parcels c. All Utility lines d. Property line distances e. Setback distances 2.COMMENT: Zoning cannot approve the building permit until final plat S20-062 has completed its pending inspections. If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |