Permit Number: T22CM07519
Parcel: 11204211A

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T22CM07519
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2022 ANY ELECTRICAL-COMMERCIAL REVIEW Active
10/04/2022 JPEELDA1 FIRE REVIEW Reqs Change The building or structures constructed shall be within 400' of a fire hydrant and or additional hydrants shall be installed or fire sprinklers throughout the complete building. Hydrants in place exceed 400'.

Questions:

Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
Tucson Fire Department
10/13/2022 LEVANS2 ENGINEERING REVIEW Reqs Change The building expansion must be submitted as a Development Package because it causes changes to the site. Please do so at this link:https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”. The site plan shall meet the requirements of AM Section 2-06 and TSM Section 2. Please also follow the procedures and guidelines outlined in City of Tucson Technical Standards Manual 9-01.2

Lianne Evans
lianne.evans@tucsonaz.gov
520-837-5341
10/18/2022 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh

PDSD Zoning Review Section

PROJECT: T22CM07519 / Commercial Addition

Plot Plan Review (1st Review)

2510 E FORT LOWELL RD/ C-1 Zone

TRANSMITTAL DATE: 10/18/2022



Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



1.COMMENT: Addition to a commercial use requires an approved development package for the site.

A Development package is a separate submittal and must be submitted and approved prior to the approval of the commercial plans.
Development Package application can be found here:

https://www.tucsonaz.gov/files/pdsd/forms/Development_Package_and_Land_Division-Subdivision_Application.pdf
For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
10/18/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the addition to the building envelope using calculations based on the 2018 International Energy Conservation Code. Reference: Section C502.1, International Energy Conservation Code 2018.
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
3. Show that the parking garage has mechanical ventilation per Section 404.1, IMC 2018.
10/18/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/18/2022 ROBERT SHERRY WATER REVIEW Passed
10/18/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM07519

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Denied
Sheet A1 Is this a S1 or S2.Conflicting information on plans. What is being Stored in Building/
Sheet A1 Additional comments may follow do to needing information additional information on existing construction and Floor plan.
Landscape sheet Coordinate with current plans.
Landscape Sheet 5 Show drive aisle leading to doors. Provide Floor Plan for existing retail space, showing ADA restrooms.
Landscape Sheet 5 Is this a solid wall?
Sheet A2 Provide details for doors. Size and hardware. Provide exit door from this space to exterior. Provide Landing at exit door.
Sheet A2 Declare use of addition.
Sheet A2 What is happing with the existing window?
Sheet A2 Is hardboard siding approved as shear panels per manufactures listing? Provide required nailing for shearwalls.
Sheet A2 Was this a required exit on existing retail space?
Sheet A2 Provide detail of new opening on existing opening?
Sheet A3 Provide manufactures cut sheet showing I-Joist can span 28 ft
Sheet A3 Show detail at EVE for I-Joist
Sheet A3 Provide details for attaching roof rafters and wall to existing.
Sheet A3 Theres a conflict with the existing building plans this area does not appear on the plan. Need existing floor plan to complete the review.
Verify it complies with 2018 IBC


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/18/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change Impact fees will be assessed once zoning review is completed