Permit Number: T22CM07445
Parcel: 13322424D

Review Status: Active

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM07445
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2022 ANY WATER REVIEW Active
10/03/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM07445

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Indicate on plans correct code years in "Code Data and Square Footage" city is on 2018 ICC code family and 2017 NEC.
2. Plans indicate Basic Wind Speed of 90MPH - Tucson indicates: Section 1609.1.1 Determination of wind loads. REVISE Section by ADDING the following after the last paragraph: Per the Basic Wind Speed Figures, use the following: Risk Category I – 100 mph Risk Category II – 105 mph Risk Category III – 110 mph Risk Category IV – 115 mph - Correct plans
3. Title sheet indicates electrical plans; however, no electrical plans in submitted documents.
Plan review stopped due to incomplete plans.


BUILDING REVIEW COMMENTS:
Denied
1. Indicate on plans correct code years in "Code Data and Square Footage" city is on 2018 ICC code family and 2017 NEC.
2. Plans indicate Basic Wind Speed of 90MPH - Tucson indicates: Section 1609.1.1 Determination of wind loads. REVISE Section by ADDING the following after the last paragraph: Per the Basic Wind Speed Figures, use the following: Risk Category I – 100 mph Risk Category II – 105 mph Risk Category III – 110 mph Risk Category IV – 115 mph - Correct plans
3. Title sheet indicates electrical plans; however, no electrical plans in submitted documents.
Plan review stopped due to incomplete plans.


MECHANICAL REVIEW COMMENTS:
Denied
1. Indicate on plans correct code years in "Code Data and Square Footage" city is on 2018 ICC code family and 2017 NEC.
2. Plans indicate Basic Wind Speed of 90MPH - Tucson indicates: Section 1609.1.1 Determination of wind loads. REVISE Section by ADDING the following after the last paragraph: Per the Basic Wind Speed Figures, use the following: Risk Category I – 100 mph Risk Category II – 105 mph Risk Category III – 110 mph Risk Category IV – 115 mph - Correct plans
3. Title sheet indicates electrical plans; however, no electrical plans in submitted documents.
Plan review stopped due to incomplete plans.


ELECTRICAL REVIEW COMMENTS
Denied
1. Indicate on plans correct code years in "Code Data and Square Footage" city is on 2018 ICC code family and 2017 NEC.
2. Plans indicate Basic Wind Speed of 90MPH - Tucson indicates: Section 1609.1.1 Determination of wind loads. REVISE Section by ADDING the following after the last paragraph: Per the Basic Wind Speed Figures, use the following: Risk Category I – 100 mph Risk Category II – 105 mph Risk Category III – 110 mph Risk Category IV – 115 mph - Correct plans
3. Title sheet indicates electrical plans; however, no electrical plans in submitted documents.
Plan review stopped due to incomplete plans.

PLUMBING REVIEW COMMENTS:
Denied
1. Indicate on plans correct code years in "Code Data and Square Footage" city is on 2018 ICC code family and 2017 NEC.
2. Plans indicate Basic Wind Speed of 90MPH - Tucson indicates: Section 1609.1.1 Determination of wind loads. REVISE Section by ADDING the following after the last paragraph: Per the Basic Wind Speed Figures, use the following: Risk Category I – 100 mph Risk Category II – 105 mph Risk Category III – 110 mph Risk Category IV – 115 mph - Correct plans
3. Title sheet indicates electrical plans; however, no electrical plans in submitted documents.
Plan review stopped due to incomplete plans.



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/04/2022 JPEELDA1 FIRE REVIEW Reqs Change Plans reference the wrong ICC code books. We are in the 2018 code cycle. Please update
Plans shall show if the building has fire sprinklers
Building address shall be shown on the plans and compliant with the TFD address requirements found on our website under permits and resources for amendments.

Questions:

Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
Tucson Fire Department
10/19/2022 STEVE SHIELDS ZONING REVIEW Approved
10/19/2022 SHASEMA1 ENGINEERING REVIEW Reqs Change 1. With the proposed modification of the existing trash enclosure a Development Package will be required that shows the new trash collection maneuverability and that the trash enclosure is built per code (Technical Standards Manual section 8).

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
10/19/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed