Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM07444
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM07444
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2022 SHASEMA1 ENGINEERING REVIEW Passed
10/03/2022 JVINCEN1 FIRE REVIEW Approved
10/11/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM07444


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Denied
Sheet A1 Provide a response letter addressing all redlined comments. Bubble or highlight all redline corrections

Sheet A3 Provide details for the new glass wall. Provide Structural details for new Steel Column.
Sheet A3 Provide Structural Calculations and details for new Overhead Security Door.
Sheet A3 Provide details for POS counter showing compliance with ADAAG.
Sheet A3 Show that existing sinks provide faucets are accessible per ADAAG.
Sheet A3 Provide clear space floor access space to Hand Sink per ADAAG
Sheet A3 Show Accessible Seating per ADAAG.
Sheet A3 Provide detail for minimum Strike side clearances at interior door. provide dimensions on plan
Sheet A3 Are you providing any hardware on this door?




If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/18/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/18/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/18/2022 ROBERT SHERRY WATER REVIEW Completed
10/18/2022 WBERGER1 ZONING REVIEW Approved
10/18/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/19/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved