Permit Number: T22CM07437
Parcel: 117067290

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T22CM07437
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2022 SHASEMA1 ENGINEERING REVIEW Passed
10/04/2022 JPEELDA1 FIRE REVIEW Approved
10/14/2022 IMONSHI1 ZONING REVIEW Approved
10/14/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
10/18/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/18/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Correct the equipment tags shown in the partial water isometric to agree with the equipment tags shown on the plumbing water floor plan. Reference: Section 107.2.1, IBC 2018.
2. Verify the total natural gas demand for the existing water heater. The gas meter load chart shows 199 MBH for the unit but the gas diagram shows a demand of 250 MBH. Reference: Section 402.1, IFGC 2018.
3. Verify the size of the existing gas pipe with the new loads. Based on Table 402.4(2), IFGC 2018, The existing 2" main gas pipe is under-sized.
10/18/2022 ROBERT SHERRY WATER REVIEW Completed
10/18/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM07437

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Denied
Sheet A3 Provide expanded plans of restrooms showing compliance with ADAAG Requirements. Provide exit signs
Sheet A3 Provide Accessible Counter at POS.
Sheet A3 Provide accessible path of travel to accessible parking and the public way. Provide accessible parking layout.
Sheet A3 Provide detail of counter height for accessibility.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/20/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved