Review Details: OTHER
Permit Number - T22CM07418
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/27/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 10/14/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Approv-Cond | Activity Number: T22CM07418 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Conditionally Approved 1. 2018 IFC 1204.2.1.1 & 1204.2.1.2. Provide 36" pathway to ridge and 18" setback from ridge MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Conditionally Approved 1. 2017 NEC Table C.1 - Min. 3/4" EMT or larger required for circuit #4 (Total PV AC Circuit) PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/14/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |