Permit Number: T22CM07378
Parcel: 12620001C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM07378
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2022 JVINCEN1 FIRE REVIEW Approved
09/28/2022 SHASEMA1 ENGINEERING REVIEW Reqs Change Engineering cannot approve build permit until its associated Development Package is approved

Scott Haseman
scott.haseman@tucsonaz.gov
09/29/2022 EHAMBLI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/17/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM07378

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Refer to page Structural Calculations page 4 of 15, Fence Post Footing. Calculations are provided for 8 feet spacing. Refer to Drawings DD5.3P and DD5.5P. It shows Gates of 20 feet and 16’-5 ¼”, also the spacing between Foundations are shown as 10 feet. Verify and submit revised Structural Calculations.
2. All additional Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018. Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
EN3.1 ELECTRICAL DETAILS AND SCHEDULES: Fault current calculation #9 seems in error. However, calculation results in a more conservative value for Fault current.


PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/19/2022 STEVE SHIELDS ZONING REVIEW Reqs Change Unitl DP22-0261 is approved Zoning cannot approve this plan
10/19/2022 JGARCIA1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2022 NGARCIA3 OUT TO CUSTOMER Completed