Permit Number: T22CM07353
Parcel: Unknown

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM07353
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comment and provide a written response.
1 Indicate revised feeder conduit, conductor sizes and types for the increased OCPD's.
2 Clarify ELECTRICAL KEYNOTE #11. 200 amp feeder to supply 100 amp equipment.
3 Provide an up to date sealed electrical plan.
2018 IBC section 107.2.1, 2017 NEC art's 240, 310.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/18/2022 VVERA1 OUT TO CUSTOMER Completed