Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM07353
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comment and provide a written response. 1 Indicate revised feeder conduit, conductor sizes and types for the increased OCPD's. 2 Clarify ELECTRICAL KEYNOTE #11. 200 amp feeder to supply 100 amp equipment. 3 Provide an up to date sealed electrical plan. 2018 IBC section 107.2.1, 2017 NEC art's 240, 310. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/18/2022 | VVERA1 | OUT TO CUSTOMER | Completed |