Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM07309
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/23/2022 | SHASEMA1 | ENGINEERING | REVIEW | Passed | |
| 10/03/2022 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 10/10/2022 | WBERGER1 | ZONING | REVIEW | Approved | |
| 10/10/2022 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/13/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 10/13/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/13/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/18/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/19/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Completed |