Permit Number: T22CM07300
Parcel: Unknown

Review Status: Active

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM07300
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2022 ANY WATER REVIEW Active
09/22/2022 VFLORES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change Need suite number.Please contact Pima County Addressing if you are not sure. Phone #:520-724-9512 Email: addressing@pima.gov
09/23/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/30/2022 JVINCEN1 FIRE REVIEW Approved
10/06/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM07300

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Denied
1. Provide all drawings and details for the Type I hood.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
1. All grease laden waste must be disposed into the grease interceptor. There are couple sinks and floor drains that do not drain to the interceptor. All of these fixtures have the potential of taking grease laden waste


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/13/2022 PAUL CAMARENA ZONING REVIEW Approved
10/13/2022 PCAMARE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed