Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM07293
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/22/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 10/03/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM07293 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1. Show the size and total number and spacing of lag bolts. 2. Provide sufficient standoffs for achieving a point load calculation under 45 pounds, R301.1. BUILDING REVIEW COMMENTS: Denied 1. R324.6.2 Set back at ridge. For arrays over 33 percent of roof a 36 " set back is required. Provide coverage calculation and show modules in position to achieve this requirement. 2. Not fewer than 2 pathways must be show from lowest roof edge to ridge R324.6.1 MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Approved Electrical calculations and load calculations approved PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/04/2022 | VVERA1 | OUT TO CUSTOMER | Completed |