Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2022 RPARSON1 OIP REVIEW Completed
10/03/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM07293

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1. Show the size and total number and spacing of lag bolts.
2. Provide sufficient standoffs for achieving a point load calculation under 45 pounds, R301.1.


BUILDING REVIEW COMMENTS:
Denied
1. R324.6.2 Set back at ridge. For arrays over 33 percent of roof a 36 " set back is required. Provide coverage calculation and show modules in position to achieve this requirement.
2. Not fewer than 2 pathways must be show from lowest roof edge to ridge R324.6.1


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Approved
Electrical calculations and load calculations approved

PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2022 VVERA1 OUT TO CUSTOMER Completed