Permit Number: T22CM07287
Parcel: 136171810

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM07287
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2022 RPARSON1 OIP REVIEW Completed
10/03/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM07287

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1.
2. Provide sufficient standoffs for achieving a point load calculation under 45 pounds, R301.1. Provide calculations


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2022 VVERA1 OUT TO CUSTOMER Completed