Permit Number: T22CM07276
Parcel: 134100200

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM07276
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/26/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM07276
Addition
8021 E SCARLETT ST Zoning R-1

TRANSMITTAL DATE:?September 26, 2022


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: Provide a Residential Plot Plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. This shall in include:
a. Lot coverage calculation that meets the requirements of UDC Article 6.4.3 & the example shown on the residential plot requirements.
b. Zoning of adjacent parcels
c. All Utility lines
d. Property line distances
In the link provided below is a Plot plan grid that can be used.
https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Grid.pdf



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
10/04/2022 JCARLTO1 NPPO REVIEW Passed
10/10/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM07276

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. Place the code reference on the plans.

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

Provide a site plan showing all buildings and utilities, R106.1.1. Show the location of utility lines to the existing building.

FLOOR PLAN:

Provide a floor plan showing each proposed room with labeled function and dimensions. Show door locations and window sizes with type identified as XO or SH. Include the identification of adjacent rooms with door or window opening into the proposed space. A bedroom egress pathway may not be enclosed.

SECTIONS - DETAILS:

Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12" x 12" continuous #4 rebar reinforced footing, R403.1. Show exterior wood siding, sheathing and wall framing anchored with ½" x 10" bolts and with pressure treated sill. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground, R317.1 item 5.

The framed wall may require a stem for achieving the 6” clearance between framing and ground (R317.1 item 5) or the floor level could be raised a minimum of 6" above grade.

ELECTRICAL PLANS:

1. Show at least one wall switch controlled light at outdoor entrances or exits, E3903.3.

OUTDOOR LIGHTING CODE

Provide any alterations with details showing compliant fixtures. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations or show proposed fixtures as Full Cut Off (night sky friendly).