Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2022 RPARSON1 OIP REVIEW Completed
10/03/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM07271

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1.


BUILDING REVIEW COMMENTS:
Approved
Addition of 16 modules to existing PV system approved.


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Denied
1. Main breaker replacement may not negatively affect the equipment integrity or listing, NEC 110.3. Provide an electrical load calculation if reducing the main breaker rating.